TX7330 LCD Repeater Panel is designed with built-in MCU processor to display exact fire event messages from the control panel and fast relay response with simultaneous audible and visual signal output. This repeater panel can also program to limit the zone display from All Zones into a particular zone or three adjacent zones through the panel key buttons. The unit is connected through the communication loop of TX7004 Intelligent control panel along with the devices and can install up to 254 units per loop. The repeater panel can be used whenever there is a need to relay information to multipoint informing key personnel.
Compliance : EN 54-2: 1997+A1: 2006
Input Voltage : Loop Power: 24VDC [16V to 28V]
External PSU : 24VDC [20 to 28V]
Current Consumption : Loop: Standby: 1mA, Alarm: 1.2mA
External PSU: : Standby: 25mA, Alarm: 80mA
Memory Capacity : Up to 300 fire event history
Number per loop : Up to 254 units (ideal)
Material / Colour : ABS / White Glossy finishing
Dimension / LWH : 180mm x 110 mm x44 mm
Weight : 300g (with Base), 256g (without Base)
Operating Temperature : 0°C to +40°C