The TX7008  intelligent addressable fire alarm control panel comprise of a range of analogue addressable, microprocessor based fire alarm control equipment to offer flexibility in both design and operation. The System is modular concept for easy tailoring of system design, to meet the full requirements of the project. The TX7008 Intelligent Fire Alarm Control Panel is designed and manufactured to meet the requirement of BS EN54 Part 2&4.

 

The TX7008  intelligent addressable fire alarm control panel is designed to provide early warning fire detection, to quickly identify the location of fire and provide user definable text informing the occupants of the building of potential smoke spread. Simultaneously, the TX7008  intelligent addressable fire alarm control panel will alert and evacuate the occupants spread. Simultaneously, the TX7008 will alert and evacuate the occupants, and control all necessary auxiliary command functions such as elevator control, air handling shut down, gas shut off & damper control , as per the cause and effects requirements configured though Command Builder Set-up.

Feature and Benefits

• Compliance EN54-2 & N54-4
• Using advance microprocessor technology with Large memory capacity
• Enhance user interface combining LCD Touch screen and keypad access
• Support real time visual algorithm
• Enhance false alarm prevention
• Keypad and PC programming
• Support Multiple interface protocol such as USB/Can Bus
• Support Loop Powered devices for extra saving on cable cost
• Built-In Printer and 160 LED Zones Indicators
• The Main board built-in USB port(Type B) for programming.

Commissioning Advantage

• Auto Enrolling of Devices
• Loop Mapping with colour coding status 
• Monitor device mismatch and dual address conflict 
• With Loop protection against power surge 
• One-man test with On/Off sounder 
• Command Builder to create requirements for fire event scenario 
• Programming Protection

Technical Specification

Compliance : EN54-2 & 4

"

Power Rating
Input Voltage : 230VAC +10%-15%, 50/60Hz(120VAC, 60Hz, it is not applicable for EN54 & Not tested by LPCB)
Input Current Consumption : 1.3 A
PSU Output to CIE : 21.5 to 28.5 VDC
Batteries : Maximum Charge Capacity: 2 x 12V / 45AH
                Maximum Charge Current: 1.7A
                I maxA: 1.41A
                I maxB: 3.01A
                Minimum Quiescent Current: 0.45A(Imin)
                Maximum Internal Resistance: 1.0Ω
                Rechargeable-Lead acid type battery
Recommended manufacturer : PG-12V42 FR 12V45AH (Tested With CIE By LPCB) and model of battery
 
Networking and Interfaces
Panel to panel communication : Can Bus [loop]
Number of Panels : 512
Interface Port : USB
 
System Capacity
Memory [Non-Volatile] : 1000 Fire Events, 10,000 General
Event Zones : 3,000 programmable
Total Group : 3,000 programmable
Sounder Group : 1,000 programmable
Common Group : 2,000 programmable
 
 
Panel Input/outputs
Programmable Relays : 4 circuits, Normally Open/Close
Programmable Input : 1 Circuit, Power limited 24Vdc (for future use)
Programmable Auxiliary Power : 19 ~ 28 VDC (Note: Current Limited)
Fixed Outputs (FPE/Sounder) : 2 Circuits, 18~28 VDC (Note: Current Limited)
Indicator : 24 LED Status/ 160 Zone Indicators
Display : 7” TFT TouchScreen
Keypad : 5 Brigade buttons and Programming Keypad
 
Material/ Color : Flat sheet Metal / with outer glass door, Orange stripe
Dimension Lx W x H : 550 mm x 510 mm x 222 mm
 
×