Overview
TXC7141 conventional manual call button has a beautiful structure and wiring is easy and reliable. After the fire is manually confirmed, press the plastic dome on the manual button to send the alarm signal to the controller. After the controller receives the alarm signal, the indicator in the corresponding area is on and an alarm sounds.
Technical Features
Operating Voltage |
DC24V, 16-28V |
Operating Current |
Normal current: ≤20uA Alarm current: ≤30mA |
Output capacity |
rated DC30V/0.1A passive output contact signal and contact resistance ≤100mΩ |
Type of starting parts | Reusable |
Start type |
Press plastic dome manually |
Reset type |
A special key is used to reset it. After an alarm is sent, open key cover of manual button and insert the key to rotate by 90°to the right |
Wiring system |
two-wire system, non-polarity |
Operating environment | Indoors, temperature -10'℃ ~ +55'℃, relative humidity ≤95%RH, without condensation |
Housing material and color | Plastic, red |
Outline dimension | 90.0mm×90.0mm×34.0mm (with base) |
Weight | about 90g (with base) |