The unit manufactured base on the requirement of EN 54 part 18, European Standard. The unit is aesthetically pleasing with unobtrusive design that will complement modern building designs and its plug-in type assembles make installation and maintenance more convenient to the installer. The unit is compatible to the TX7004 Analogue Intelligent Fire Alarm Control Panel, produced by single manufacture T&A, to avoid addressable communication compatibility problem.
Share this:

Overview

 

The TX7210 Addressable Single Input/output Module is characterized as one input or output volt free relay and control module. The TX7210 unit is normally used for overriding equipment such as lift return, door holder, smoke extract fans, air handling unit, auto dialler to fire brigade, BMS and etc. The unit has built-in feedback signal feature, according to the pre-configured interface module command fire scenario, the alarm controller send out start command to the equipment required to start. After receiving the command, output module enables its relay to change state. Once the module is under control and operated a confirmation signal will be sending back to the alarm controller. In addition, the TX7210 addressable single input/output module unit incorporates an intelligent processor that provides automatic monitoring for both open and short circuit of the input signal line.

Feature and Benefits

• EN54-18:2005 Compliance

• LPCB Approved

• Built-in MCU processor and digital addressing

• 24Vdc/3A Output relay contact and Control module

• Input Fire or Supervisory signal configuration

• LED status indicator

• Onsite Adjustable Parameter

• Loop or external power input

•  Aesthetically pleasing design

• Surface mounting with fix base for simple installation

Technical Specification

Listed : LPCB / CE-CPR

Compliance : EN54-18:2005

 

Power Rating

Input Voltage : Loop Power:24VDC [16V to 28V] External PSU: 20 to 28VDC

Current Consumption : Loop: Standby 0.6mA, Alarm: 1.6mA

External PSU: Standby 0.6mA, Alarm: 45mA

Control output voltage : 24VDC / 2A rating

 

Module

Input Relay : Normally Open dry contact

Input Resistance : 5.1Kohms/ ¼ W

Protocol/Addressing : T&A, Value range from 1 to 254

Indicator Status : Normal: Single blink/Active: Steady/Fault: Double Blink

 

Material / Colour : ABS / White Glossy finishing

Dimension / LWH : 108 mm x 86 mm x38 mm

Weight : 170g (with Base), 92g (without Base)

Operating Temperature : -10°C to +50°C

Ingress Protection Rating : IP30

Humidity : 0 to 95% Relative Humidity, Non condensing

×