Copyright © 2021 TANDA Development Pte. Ltd. All rights reserved.Privacy Policy.Site MapDesigned by

• EN54-12 Certified
• Hassle free alignment, built with digital guide display and laser beam pointing
• Employ single-ended design through reflective mirror Four ranges wide monitoring from 8-100 meters via encoder
• Three users programming sensitivity adjustment
• Built-in microprocessor
• Self-diagnosis function can monitor for internal faults Automatic compensation for factors weakening received signals, such as dust contamination, positional movement and ageing of the transmitter
• Fire and Fault interfacing relays
• Attractive and pleasing appearance
• Real User friendly alignment method
Listed |
LPCB / CE-CPR |
Compliance |
EN54-12:2015 |
Fire Detection and Alarm Systems |
BS 5839 Part 1:2002 |
Operating Voltage |
20 V to 28 V DC |
Current Parameters |
Standby:23mA Commission:56mA Alarm:33mA |
Beam Sensor Sensitivity [via Encoder] |
Level 1: 2.6 dB High Sensitivity Level 2: 3.8 dB Medium Sensitivity Level 3: 5.8 dB Low Sensitivity |
Beam Pathway Length [via Encoder] |
Span 1: 8 to 20 meters limited Path (1x mirror reflector required)
Span 2: 20 to 40 meters Short Path (1x mirror reflector required) Span 3: 40 to 70 meters Normal Path (4x mirror reflector required) Span 4: 70 to 100 meters Long Path (4x mirror reflector required) |
Beam Path Angle |
±0.5º Directional |
Digital Display Guide |
Nixie Tube |
LED Indicator Guide |
Red: Fire; Yellow: Fault; Green: Alignment |
Capacity [Fire & Fault] |
Normally Open/ 2.0 A; 30 VDC |
Material / Colour |
ABS / White |
Dimension / Weight |
L:190.87 x W:126.87 x H:91.96 mm / 440 gm |
Weight |
0.130 Kg with base |
Accessories |
Mounting Bracket/ TX7130-R 4 x Mirror Reflector |
Operating Temperature / Protection Rating |
-10°C to 55°C / IP30 [IP66 glue seal-For permanent fixing] |
Humidity |
0 to 95% Relative Humidity, Non condensing |
Installation and Operation Manual of TX7130 Conventional Reflective Beam Detector