Feature and Benefits

• Self-check is available

• Auto/Manual mode

• The monitor can be muted automatically to eliminate audio return while the microphone is

used to broadcast

• As it receives the emergency signal, the power amplifier can automatically adjust audio to

preset position not controlled by the volume potentiometer, eliminating the influence of

human operation

• Automatically switching between the main power and the standby power

• Fault uploading

• Over heat protection

• Providing 24VDC off-set for local audio output line and line-checking module

• Communicate with TG7100 Broadcast Control Panel through RS485

Technical Specification

The Main Power

220VAC(187V~242V)\50HZ

Standby Power

 220VAC(187V~242V)50Hz

Local Address

1~10(binary code, no repeated codes)

Input Resistance

10KΩ

Input Level

 775mV

Stable Voltage Output

120V

Frequency Response

80Hz~8KHz(90V~145V)

Harmonic Distortion

≤5%

Noise Level

<37mV

Dimension Lx W x H

483.0mm×330.0mm×88.5mm

Weight

6.5 Kg

Operating Temperature

-10°C to +40°C

Relative Humidity

≤95% Relative Humidity, Non condensing

 

×